                  This particular case began at 12:58 p.m. on July 30, 2013. The cause of the fire

               was an overload of the secondary coil of the pole transformer, which led to insulation
               deterioration, causing a short circuit between the coil layers as well as a rapid increase in
               the temperature of the transformer. The oil from the transformer´s insulation then ignited,
               which culminated in the spread of the fire. The pole transformer in this case was located
               in an urban area. After the insulation oil ignited, the instantaneous chain reaction caused
               severe burning of three residential houses. To serve as a reference for similar causes of fire,
               this study will use the preceding incident for a case analysis.






               簡介                                              成正比,若2次側線圈數(N2)大於1次側

                (一)變壓器                                         線圈數(N1),則該變壓器為「升壓變壓
                       變壓器是利用電能與磁能轉換感應                         器」,反之則為「降壓變壓器」。
                       的原理,將 2 組線圈繞製在共同的                         (二)臺電配電線路
                       「鐵芯」上,如下圖所示,連接電                                 臺電系統大型核、水、火力發電廠

                       源端的稱為「1 次線圈」或「主線                                產 生 電 力 後, 需 由 變 壓 器 升 壓 至
                       圈」,連接負載端的稱為「2 次線圈」                              345kV 利用輸電線路輸送,並透過
                       或「副線圈」。                                         超高壓變電所、1 次變電所等變電所
                                                                       分別降壓為 161kV、69kV 提供科
                                                                       學園區、工業區、高鐵和捷運等大
                          V1                     V2
                                                                       型用戶電力,並透過配電變電所、
                                                                       2 次變電所及配電系統再降壓分配提
                                                                       供一般用戶或民生用電。假若電廠
                   AC                                                  發電或輸電線或變電所供、輸電能
                                                   R                   力不足,都會影響供電。
                                   N1    N2
                                                                (三)桿上變壓器
                                                                       臺電公司對於架空配電線路皆採用
                                                                       桿上變壓器,其 1 次高壓側之電壓
                                                                       為 6,900 伏特,將電壓降至 110 伏
                           1次線圈           2次線圈                         特或 220 伏特後,供電予用戶使用;

                 ◆ ◆變壓器原理示意圖                                           桿上變壓器之裝置數量約達 79 萬 7
                                                                       千餘具(統計至 100 年底),可分
                    當1次線圈接上交流電源,於該線圈通                                  為普通型、改良型及密封型等類型。
               過的電流會在鐵芯中產生磁通量變化,另1                                  1. 普通型桿上變壓器:該型變壓器雖構

               端的2次線圈會因為感應的電動勢,而產生                                    造簡單及成本較低,惟保護開關外
               另一個相同頻率的交流電。法拉第定律說                                     裝、1次高壓側帶電體裸露(電線外
               明感應電動勢與磁通量以及線圈匝數的關                                     皮未具高電壓絕緣能力,故仍視同裸

               係,在理想情況下,感應電壓與線圈匝數                                     線),皆為高電壓設施。